Honeywell MMI810.1 mod.40-34 gas control box designed for two-stage burners with forced draft, as well as for gas-oil combination burners.
Compatible flame detectors include:
- Ionization sensor
- Infrared flicker sensor
Resideo MMI810.1 mod.40-34 automatic gas firing device technical data:
- Waiting time at start position: 9 secs approx
- Pre-purge time: 34 sec
- Pre-ignition time: Nil Ignition safety
- Time ts1: 5 secs max
- Approx. delay time to main flame: 10 sec approx
- Main flame establishment time ts2: 5 secs max
- Operating voltage 220 / 240 V (-15… +10%) 50 Hz (50 – 60 Hz)
- Fuse rating: max. 10 A rapid, 6 A slow
- Power consumption: 10 VA
- Amplifier sensitivity: 1 µA
- Min. current from UV tube or ionisation probe: 5 µA
- Flame detector cable: max. 20 m cable length
- Air pressure monitor: working contact 4 A, 230 V
- Infrared flare detector: IRD 1020
- Weight incl. base: 350 g
- Mounting attitude: any
- Insulation standard: IP 44
- Permissable ambient temp.: -20° C… +60°C
- Classified acc. to EN 298: BTLLXN