Resideo DVI980N mod.04 for 1-stage forced draught and atmospheric gas burners, with DC valves Possible flame detectors:
- Ionisation probe
- Infrared flicker detector 1020.1
- UV flame sensor UVD 971
Honeywell DVI980N mod.04 gas control box technical data:
- Operating voltage 220 / 240 V (-15… +10%)
- Power consumption: ca. 12 VA
- Total load: max. 6 A during 0,5 sec
- Air proving switch: 1 working contact
- STB Safety temperature delimiter: 1 working contact
- Ignition frequency: up to 40 Hz
- Energy ignition spark: 10 µAs
- Ignition voltage: 20 kV
- Sensitivity (operation): 1 µA
- Min. required ion. current: 1.5 µA
- Sensitivity for stray light: 0.4µA
- Flame signal output: Optocoupler max 70V DC/100mA
- Stray capacity: Probe – earth less than 1000 pF
- Cable length: < 3 m
- Flame detectors IRD 1020.1: end-on viewing
- UVD 971: end-on viewing
- Weight incl. Wiring base: 190 g
- Mounting position: any
- Protection class: IP 40
Satronic DVI980N mod.04 automatic gas firing device controls and supervises forced draught and atmospheric gasburners. Satronic DVI980N mod.04 control box approved and certified according to the applicable European standards and regulations. The use on direct air heaters according DIN 4794 is also possible.