Honeywell DKW 976-N mod.05 0426005 control box

SKU: 0426005, 852.124.209

Price on request

5 People watching this product now!

Satronic DKW976-N mod.05 0426005 gas burner safety contol box designed for diesel burners on air heaters and those with a capacity exceeding 30 kg/h, supporting intermittent operation with or without fuel preheating. Resideo DKW976-N mod.05 control unit compatible with 1- and 2-stage systems, providing restart and ventilation after flame loss.

Compatible flame sensors include:

  • Photoresistor MZ 770 S
  • Infrared sensor IRD 1010.1
  • Ultraviolet sensor UVD 970

Honeywell DKW976-N mod.05 gas control unit technical data:

  • Subsequent ventilation after the flame disappears during operation: 60 s
  • Flame sensor cable length: < 2 m
  • Weight including base: 190 g
  • Installation position: any
  • Protection class: IP 40
  • Permissible climatic conditions for the device and flame sensor: humidity max. 95% at 30°C
  • Ice formation, water exposure and condensation are not allowed
  • Approved in accordance with European standards EN 230, as well as other relevant directives and standards
Brand