Resideo DLG976 mod.02 0366002 control unit for 2-stage forced draught and combi oil/gas burners.

Possible flame detectors:

  • Ionisation probe
  • Infrared flicker detector 1020
  • UV flame sensor UVD 971

Honeywell DLG976 mod.02 gas burner control technical data:

  • Operating voltage: 220 / 240 V (-15… +10%)
  • Air proving switch: 1 working contact 4 A, 230V
  • Sensitivity (operation): 1 µA
  • Min. required ion. current: 1.5 µA
  • Sensitivity for stray light: 0.4 µA
  • Cable length: < 3 m
  • Weight incl. wiring base: 190 g
  • Mounting position: any
  • Protection class: IP 40
  • Approved ambient parameter for control and flame detector max. 95% at 30°C
  • Build-up of ice, penetration of water and condensing water are inadmissible
  • Approvals according to European standards EN 298 and EN 230, as well as all other relevant Directives and standards
  • Classified acc. to EN 298 FTLLXN