SKU: 88600204, 624.103.156
Price on request
2 People watching this product now!
Kromschroeder 88600204 BCU370WI2FEU0D3 control unit controls, ignites and monitors industrial forced draught burners of unlimited capacity in intermittent or continuous operation.
Kromschroder BCU370WI2FEU0D3 88600204 gas burner safety control box technical data
- Mains voltage: 230 V AC, 50/60 Hz
- Flame control with UV sensor or ionisation sensor
- Flame signal for Ionization control: 1 – 28 μA, UV control: 1 – 35 μA
- For intermittent or continuous operation
- Air pressure check during pre-purge and operation by external air pressure switch DL
- Maximum length of ignition cable with integrated electronic ignition: 1 m
- Maximum length of ionisation/UV cable: 50 m (164 ft)
- Max. number of operating cycles: 250,000
- Ambient temperature: -20 – +60 °C (-4 – +140 °F)
- Enclosure: IP 54 pursuant to IEC 529
- Housing made of impact-resistant and heat-resistant plastic. Plug-in upper section with operating and display elements.
- Lower section with connection terminals, earthing strip and pre-wired neutral bus with spacious wiring chamber
- Electronic ignition, double-pole
- Fan control: 3 A relay
- Valve control: three-point step
- Flame control: ionization control (continuous or intermittent operation) or UV control
- intermittent operation with UVS)
- Digital input function: integrated tightness control
- With bottom section
- Minimum burner pause time tBP: 0 s
- Burner start-up attempts: 4
- Switch-on delay time tE: 0 s
- Pre-ignition time tVZ: 3 s
- Safety time 1, burner/pilot burner start-up tSA1: 3 s
- Flame proving period 1, burner/pilot tFS1: 2 s
- Safety time 2, main burner start-up tSA2: 0 s
- Flame proving period 2, main burner tFS2: 0 s
- Controller enable signal delay time tRF: 30 s
- Minimum burner on time tB: 0 s
- Safety time during operation tSB: 1 s
- V2 during burner operation: On
- Behaviour in the event of flame failure during operation: restart
- Burner switch-off threshold: 1 micro A
- UVS check (1 x in 24 hours): Off
- Operating time in Manual mode: limited to 5 minutes
- User-defined password
- Air monitoring during pre-purge: On
- Air monitoring during operation: On
- Gas pressure monitoring: On
- Digital input function: integrated tightness control
- TC test period tP: 10 s
- Fan run-up time tGV: 5 s
- Valve control: On
- Pre-purge on each start-up: On
- Pre-purge time tPV: 20 s
- Post-purge time tPN: 10 s
- Weight: 1.8 kg
Brand |
---|