SKU:
84765713, 624.103.146
Price on request
5
People watching this product now!
The Kromschroder TC 3R05Q/Q 84765713 tightness control unit designed to test the tightness of two automatic shut-off valves before burner ignition or after shutdown.
It features adjustable pressure testing time, enabling adaptation to different volumes, permissible leak rates, and inlet pressures.
The Kromschroder TC 3R05Q/Q 84765713 tightness control compatible with solenoid valves that can open quickly or slowly, including those with starting load functionality.
Kromschroder TC 3R05Q/Q 84765713 tightness control technical data:
- Weight: 1, 49 kg
- F1: protection of valve outputs (terminals 15
and 16), fault signal (terminal 12) and supply of the control inputs (terminals 2,7 and 8). - F2: protection of the safety interlock/controller enable signal (terminal 6).
- The input current at terminal 1 must not exceed 5 A.
- TC switching cycles: 250,000 pursuant to EN 13611.
- Reset: using a button on the device or by remote reset.
- Gas type: natural gas, town gas, LPG (gaseous), biogas (max.0.1%-by-vol. H2S) and air.
- The gas must be clean and dry in all temperature conditions and must not contain condensate.
- Inlet pressure pu: 10 to 500 mbar (3.9 to 195 “WC). Measurement time tM: 5 to 30 s, adjustable.
- Set at the factory to 30 s.
- Medium and ambient temperatures: -20 to +60°C (-4 to +140°F).
- No condensation permitted.
- Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life.
- Storage temperature: -20 to +40°C (-4 to +104°F).
- installation altitude: 2000 m AMSL.
- 5 cable glands: M16 x 1.5.
- Cable cross-section: min. 0.75 mm2 (AWG 19), max.2.5mm2 (AWG14).
- Valve opening time: 3 s.
- Housing made of impact-resistant plastic.
- Connectors: aluminium.
- Enclosure: IP 65.
Krom schroder TC 3R05Q/Q 84765713 tightness control unit certification:
Kromschroder TC 3R05Q/Q 84765713 tightness control, marked with product ID No. CE-0085CS0076, complies with the requirements of the listed Directives and Standards.
Directives:
- 2009/142/EC – GAD (valid until 20 April 2018)
- 2014/35/EU – LVD
- 2014/30/EU – EMC
Regulation:
- (EU) 2016/426 – GAR (valid from 21 April 2018)
Standards:
- EN 1643
- EN 60730
- EN 61000-6-2
- SIL 3 according to EN 61508
Brand |
---|