Kromschroeder DG500B-3 (84447450) gas pressure switch

SKU: 84447450, 624.214.025

Price on request

3 People watching this product now!

Kromschroeder DG500B-3 84447450 gas pressure switches designed to monitor changes in gas or air pressure, whether it’s increasing or decreasing.

Kromschroder 84447450 DG500B-3 gas pressure switch maintenance

To ensure smooth operation:

  1. Verify the tightness and functionality of Krom schroder DG500B-3 84447450 gas pressure switch annually, or every six months if it operates with biogas.
  2. Conduct a functional check, particularly for decreasing pressure control, for example, using the PIA.
  3. After performing maintenance work, ensure to check for any leaks in the system.

Krom schroder DG500B-3 84447450 pressure switch technical data

  • Adjusting range: 100-500 mbar
  • Gas type: natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1 %-by-vol. H2S) and air
  • Switches with rising positive pressure
  • Electrical connection via screw terminals and M16 cable gland, IP 54
  • Maximum medium and ambient temperatures: -20 to +80°C
  • Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life
  • Storage temperature: -20 to +40°C
  • Diaphragm pressure switch, silicone-free
  • Diaphragm: NBR. Housing: glass fibre reinforced PBT plastic with low gas release
  • Lower housing section: AlSi 12
  • Enclosure: IP 54 or IP 65
  • Safety class: 1
  • Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG 13)
  • Line entrance: M16 x 1.5, clamping range: diameters of 4 to 10 mm
  • Electrical connection type: screw terminals
  • Weight: 0,321 kg

Kromschroeder DG500B-3 84447450 differential pressure switch designed lifetime

The provided information regarding the expected lifespan pertains to the utilization of Kromschroder 84447450 DG500B-3 differential pressure switch for monitoring both increasing and decreasing gas or air pressure, as outlined in these operational guidelines. Upon reaching the end of the designed lifespan, it becomes necessary to replace safety-critical products. The designed lifespan, determined from the date of manufacture, complies with EN 13611 and EN 1854 standards.

Krom schroder 84447450 DG500B-3 gas pressure switch certification

Krom schroder DG500B-3 84447450 pressure switch, identified with product ID No. CE-0085AP0467, complies with the requirements of the following:

Directives:

  • 2009/142/EC – Gas Appliances Directive (GAD)
  • 2014/35/EU – Low Voltage Directive (LVD)

Regulation:

  • (EU) 2016/426 – Gas Appliances Regulation (GAR)

Standards:

  • EN 13611:2015+AC:2016
  • EN 1854:2010

The relevant Kromschroeder 84447450 DG500B-3 differential pressure switch corresponds to the type tested by the notified body 0085. Production is subject to surveillance procedures as per Directive 2009/142/EC, Annex II, and Regulation (EU) 2016/426, Annex III, paragraph 3.

Brand