Kromschroeder DG10U-3 (84447300) gas pressure switch

SKU: 84447300, 624.214.003

Price on request

1 People watching this product now!

Kromschroder DG10U-3 84447300 differential pressure switch designed to monitor pressure changes in gases or air, regardless of whether it is increasing or decreasing. Kromschroeder DG10U-3 84447300  gas pressure sensors respond to any pressure deviations from the setpoint. When the set pressure is reached, a microswitch with a switching contact is switched on. The trigger level is adjusted using a handwheel.

Krom schroder DG10U-3 84447300 pressure switch technical data

Adjusting range: 1-10 mbar

Gas type: natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1 %-by-vol. H2S) and air

Switches with rising positive pressure (gas/air), negative pressure (air), differential pressure (air-air)

Electrical connection via screw terminals and M16 cable gland, IP 54

Maximum medium and ambient temperatures: -20 to +80°C

Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life

Storage temperature: -20 to +40°C

Diaphragm pressure switch, silicone-free

Diaphragm: NBR. Housing: glass fibre reinforced PBT plastic with low gas release

Lower housing section: AlSi 12

Enclosure: IP 54 or IP 65

Safety class: 1

Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG 13)

Line entrance: M16 x 1.5, clamping range: diameters of 4 to 10 mm

Electrical connection type: screw terminals

Weight: 0,321 kg

Kromschroder 84447300 DG10U-3 gas pressure switch maintenance

To ensure reliable operation of the pressure switch, Krom schroder DG10U-3 84447300 is recommended to conduct an annual leakproofness and functionality check of the device. If Kromschroder 84447300 DG10U-3 gas pressure switch is used with biogas, this period should be reduced to six months. It is also important to regularly check the functionality of Kromschroeder DG10U-3 84447300 differential pressure switch, for example, using the PIA check valve, performing pressure reduction monitoring. After carrying out maintenance, it is necessary to check the device for leaks.

Brand