Kromschroeder UVC1D1G1A (84320301) UV flame sensor

SKU: 84320301, 624.211.002

Price on request

3 People watching this product now!

Kromschroeder UVC1D1G1A 84320301 flame detector is specifically engineered for monitoring flames that emit UV radiation within industrial thermoprocessing systems. Its counterpart, the Kromschroder U84320301 VC1L1G1A UV-sensitive detector, is compatible for use in intermittent or continuous operation when paired with Kromschroder burner control units BCU and PFU.

Krom schroder UVC1D1G1A 84320301 flame detector technical data

  • Series 1
  • Quartz glass heat guard lens
  • Rp 1/2 internal thread and cooling air connection
  • M20 cable gland
  • Supply voltage: 100 to 230 V AC, 50/60 Hz (terminals L and N)
  • Length of cable between UV flame detector and burner control unit: min. 2 m, max. 100 m
  • Distance between UV flame detector and flame: 300 to 400 mm
  • UV tube: P578, spectral range: 190 to 270 nm, max. sensitivity: 210 nm ± 10 nm
  • Min. DC signal: 1 μA
  • Housing: aluminum
  • Cable gland for cable diameters of 7 to 13 mm
  • Clamping range of the connection terminals: 0.5 to 1.5 mm2
  • Weight: 1 kg
  • Ambient temperature: -20 to +80°C (-4 to +176°F)
  • Storage temperature: -20 to +80°C (-4 to +176°F)
  • Enclosure: IP 65
  • Safety class: 1
  • Pollution degree: internal environment: 2, eternal environment: 4

Kromschroder UVC1D1G1A 84320301 UV-sensitive detector designed lifetime

The provided information regarding the designated lifespan is contingent upon adhering to the operational guidelines outlined in the instructions. Upon reaching the designated lifespan, safety-critical components must be replaced. The designed lifespan of the UVC 1, based on its date of manufacture, is 10 years. Meanwhile, the UV tube is expected to last approximately 10,000 operating hours, roughly equivalent to 1 year. It’s important to note that these guidelines specifically pertain to heating systems. For thermoprocessing equipment, it is advised to adhere to local regulations.

Kromschroeder 84320301 UVC1D1G1A flame detector declaration of conformity

Krom schroder UVC1D1G1A 84320301 flame detector complies with the essential requirements of the following Directives and Standards:

Directives:

  • 2009/142/EC
  • GAD (valid until 20 April 2018)
  • 2014/30/EU
  • 2014/35/EU

Regulation:

  • (EU) 2016/426
  • GAR (valid from 21 April 2018)

The relevant Krom schroder 84320301 UVC1D1G1A UV cell corresponds to the tested type sample. The production is subject to the surveillance procedure pursuant to Directive 2009/142/EC Annex II paragraph 3 (valid until 20 April 2018) and to Regulation (EU) 2016/426 Annex III paragraph 3 (valid from 21 April 2018).

Brand