SKU: 75456344, 624.214.255
Price on request
5 People watching this product now!
Kromschroeder 75456344 DG40VC9-6W/B gas pressure switchs provide reliable control of the minimum allowable pressure drop by activating actuation, opening or switching contacts when a set point is reached.
Kromschroder DG40VC9-6W/B 75456344 pressure switch application
Krom schroder 75456344 DG40VC9-6W/B differential pressure switch designed for monitoring gas and air pressure, as well as for monitoring biomethane pressure.
Krom schroder DG40VC9-6W/B 75456344 pressure switch adjustment
1. Begin by disconnecting the system from its electrical power source to ensure safety during maintenance procedures.
2. Remove the housing cover to gain access to the internal components.
3. Utilize an ohmmeter to establish electrical connectivity and measure resistance within the system.
4. Adjust the switching point as necessary by manipulating the hand wheel, allowing for precise calibration.
5. Install a pressure gauge to monitor the system’s pressure levels accurately.
6. Gradually apply pressure to the system while closely observing both the ohmmeter readings and pressure gauge indications. This step allows for real-time monitoring of electrical resistance changes and pressure variations.
7. Fine-tune the switching point by adjusting the hand wheel accordingly, ensuring optimal functionality and performance.
8. Complete the process by securely reattaching the housing cover and restoring the electrical power supply, if required, once all maintenance tasks are completed.
Krom schroder 75456344 DG40VC9-6W/B pressure switch technical data
- Adjusting range: 5-40 mbar
- Gas type: natural gas, town gas, LPG (gaseous), flue gas, biogas and air
- Max. test pressure for testing the entire system: temporarily
- Maximum medium and ambient temperatures: -20 to +80°C
- Storage temperature: -20 to +40°C
- Diaphragm pressure switch, silicone-free
- Diaphragm: NBR
- Housing: glass fibre reinforced PBT plastic with low gas release
- Lower housing section: AlSi 12
- Enclosure: IP 54 or IP 65
- Connection for valVario controls at the bottom, pressure tap on the side opposite to the plug
- Electrical connection via 4-pin plug, with socket
- Safety class: 1
- Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG 13)
- Line entrance: M16 x 1.5, clamping range: diameters of 4 to 10 mm
- Weight: 0,083 kg
Brand |
---|