Honeywell SH113 mod.C2 03142C2 control box

SKU: 03142C2, 852.124.093

Price on request

1 People watching this product now!

Honeywell SH113 mod.C2 control unit for liquid-fuel single-stage supercharged burners for pre-heating operation, with or without heating of liquid fuel.

Possible flame sensor:

  • MZ 770 S photoresistor
  • IRD 1010 infrared detector
  • UV flame sensor UVD 970

Satronic SH113 mod.C2 automatic gas firing device technical data:

  • Maximum heating time of the fuel heater ta: 400 s
  • Pre-ventilation time and time before ignition tv1: 15 s
  • Stray light control TF: 5 s
  • Safety time ts: 5 s
  • Time after ignition tn: 7 s
  • Operating voltage: 230 V (-15…+10%) 50/60 Hz (±5%)
  • Input fuse: 10 A high-speed, 6 A inert
  • Power consumption: approximately 12 VA
  • Air pressure switch: 1 working contact 4 A, 230 V
  • Sensitivity: 1.0 µA
  • Minimum required ionization current: 1.5 µA
  • Sensitivity to outside light: 0.4 µA
  • Wire length: < 3 m
  • Weight with base: 190 g
  • Installation position: any
  • Protection: IP 40
Brand