The combined control and ignition system (CVI) is designed for use in gas boilers, heaters and water heaters equipped with an automatic ignition system. It is based on Honeywell S4565CM1047U burner control units and cooperates with VK41 series gas regulators… to provide reliable emergency protection.
Important features of the S4565CM 1047U control box include:
1. Safe Ignition: CVI guarantees safe ignition and effective flame control on the main burner of the heating system. This minimizes the risk of fire and emergency situations.
2. Flexibility of Settings: The system allows you to program ignition, monitor the flame and adjust the gas flow to both the main and pilot burner. This makes it possible to customize the ignition process for optimal efficiency and stability of the equipment.
The burner controller S4565 CM 1047U includes various modifications for different types of ignition systems:
The S4565CM1047B burner controller with a voltage of 220/240 V~ can be directly connected to the electrical circuit of the VK41 series gas regulator. It is important to note that they are not intended to directly affect the flame. They have outstanding characteristics and high reliability, and various modifications are available corresponding to different ignition systems.
General remarks
• Housing: (S) tandard or (F)lame retarding / IPX4 S/Y
• Electromagnetic filter Y
• Ambient temperature -15…60°C
• Humidity 90% R.H. max. (at 40 °C) without condensation
Electrical characteristics
• Supply voltage, power consumption 230 V AC; 50 Hz; no more than 4 VA
• Gas valves designed for VK41..G series
• 230 V AC fan; 50 Hz, not more than 1 A
Electrical connection
• Multi-faceted molex 3003 connector, suitable for molex 3001 connector
• High voltage spark and ground 2.8 x 0.5mm blade terminal
• Flame extinguishing rod 4.8 x 0.8 mm with blade terminal
Lock/Reset/Alarm
• Blocking: (N) on non-volatile or (V) on unstable N
• Shut-off without air access –
• Reset and alarm (I) ntegral or (R) emote R (neon signal 230 V, max. 1 mA)
• Constant alarm (max.1 mA) Y
Ignition
• Ignition: up to (G) round, (Cl) closed loop or 230 V (DC) G
• Ignition and extinguishing by flame: (S) separate or (C) combined S
• Flame sensor: (P) phase or phase-(N) internal P
• Spark frequency 25 Hz
• Minimum open spark voltage of 15 kV
General provisions
• All burner control protection functions are integrated into a reliable system.
• Special attention is paid to optimal solutions for systems with spark ignition of the burner (DBI) and systems with pilot burner (IP) for ignition of the main burner.
• The gas regulator and ignition regulator are designed using time-tested principles.
• The installation of the ignition regulator on the gas regulator is simplified thanks to the connector provided on the top of the regulator.
• The controller can be installed within a 90° angle in any direction from the vertical position of the two-position electric actuator.
Standards
The ignition regulator is designed in accordance with European standards:
– EN 298: Automatic control systems for gas burners.
– EN 60730-1: Automatic electrical control devices for household and similar purposes.
With regard to electrical safety, the ignition regulator can be used in installations that meet the electrical safety requirements for household electrical appliances defined by the series of European standards EN 60335.
Brand |
---|