Designed to optimize the operation of gas boilers, heaters and water heaters with an automatic ignition system, the innovative joint control and ignition system (CVI) is based on the Honeywell S4565C1132U burner control units and functions together with the VK41… series gas regulators, providing a high level of reliability and safety.
Important characteristics of the Resideo S4565C 1132U burner control unit include:
1. Safe Ignition: CVI guarantees reliable ignition and effective flame control on the main burner of the heating equipment, which significantly reduces the risk of fire and emergency situations.
2. Flexible Settings: The system provides the ability to configure the ignition process, as well as flame control and gas flow control for both the main and pilot burners, which ensures optimal efficiency and stability of the equipment.
The relay Honeywell S4565 C 1132U offers a variety of variations designed for different ignition systems:
• Spark Ignition Of The Burner (DBI): These variants of regulators ensure a safe ignition time, which is especially important for systems with spark ignition of the burner.
• Pilot Burner Ignition (IP): For systems with pilot burner ignition, regulators with the suffix BF indicate an atmospheric system with pilot burner ignition and a timer for safe ignition time.
These controllers of the Honeywell S4565C1132B control box with a voltage of 220/240 V~ can be easily connected to the electrical circuit of the VK41 series gas regulator…, but it is important to note that they do not affect the flame directly. They have outstanding characteristics and high reliability, and are also available in various modifications corresponding to various ignition systems.
General provisions
1. Comprehensive Protection: All burner protection functions are integrated into a reliable system, ensuring a high level of safety.
2. Optimal Solutions: Special attention is paid to finding optimal solutions for two types of systems: with spark ignition of the burner (DBI) and with a pilot burner (IP) for ignition of the main burner.
3. Proven Principles: The gas regulator and ignition regulator are designed using time-tested principles, guaranteeing reliability and stability of operation.
4. Simplified Installation: The installation of the ignition regulator on the gas regulator has become easier thanks to the connector located on the top of the regulator.
5. Flexible Installation: The S4565C 1132B automatic furnace can be installed within a 90° angle in any direction from the vertical position of the two-position electric actuator, which provides convenience during installation and configuration.
Reset the lock
The Honeywell S4565 C 1132B gas burner control box can be reset by pressing their own or external reset button. If the first attempt fails, you should wait at least 15 seconds before trying again.
When heating is required, the airflow control relay detects the absence of airflow and starts the fan after a time equal to the sum of the self-test period and the waiting period.
When this relay determines the sufficiency of the air flow, the built-in ignition device and the gas valve are switched on. The spark ignites the gas, and the resulting flame is detected by the flame sensor rod.
After the flame is established, a preset extended ignition time can be added.
If the flame does not set during the safe ignition time, the ignition regulator is blocked.
If the flame goes out during normal operation, the ignition controller repeats the starting sequence.
If the air flow control relay does not detect the air flow during the safe ignition time, the ignition regulator is blocked.
Standards
The burner control machine is designed in accordance with European standards:
– EN 298: Automatic control systems for gas burners.
– EN 60730-1: Automatic electrical control devices for household and similar purposes.
With regard to electrical safety, burner controller S4565C1132 can be used in installations that meet the electrical safety requirements for household electrical appliances defined by the series of European standards EN 60335.
The Honeywell 78205 automatic furnace for Viessmann is installed on the Feuerungsautomat GU1 model boiler.