Honeywell C7061A1079 UV sensor 120/230V shutter

SKU: C7061A1079/U, 534.211.014

Price on request

1 People watching this product now!

Resideo C7061A1079 is an photoresistor for combustible materials. Interacts with amplifier R7061 and relay R4348 or with amplifier R7861A and burner programmers 7800.

Terminal block for the Honeywell C7061A 1079 photo resistance – clamp type, removable screws. The sensor is installed up to 300 m from the flame control relay. Provides a closed loop with self-monitoring for reliable operation and avoiding false alarms that cause emergencies.

Features

• Two flame detectors can be connected in parallel to reduce the likelihood of false alarms in complex flame detection.

• The flame detector can be mounted on a swivel bracket.

• The UV sensor tube is designed to operate at temperatures up to -40°C (-40°F).

• When using the R7861 amplifier and the 7800 series programmer, the flap controls the ultraviolet radiation sensor, closing 12 times per minute in the control mode. When using the amplifier R7061 and the flame control relay R4348, the frequency of vibration of the damper is 60 times per minute. The microprocessor in the 7800 control unit controls the circuit.

• Detectors can be installed horizontally, vertically or at any angle. The Honeywell C7061 A 1079/B photocell with self-test requires adjustment of the front panel and support points for the correct installation of the shutter mechanism.

• Replacement of the UV sensor tube and quartz window can be carried out on site.

• A device with a built-in UV sensor monitoring function is used with the R7061 and R7861 amplifiers with dynamic self-checking.

• As an additional equipment, a quartz viewing window can be installed for high pressure (50 lb/sq. inch or 345 kPa).

Technical specifications

The Honeywell C7061A1079/B phoro unit in a standard housing with a built-in self-monitoring function has the following characteristics:

– Nominal pressure for quartz viewing window: up to 138 kPa (20 lb/sq. inch).

– Weight: 3.3 kg (7.3 lb).

– Mounting and orientation: A mounting flange with an internal thread of NPT 3/4″ is used for mounting on the sighting pipe.

– Connection: Cable with multicolored cores conforming to NEC Class 1, 8 feet (2.4 m) long.

– Operating range of the external air: -40°C to +70°C (-40°F to +160°F) with a decrease in the maximum temperature by 1°F for every 13°F of the temperature on the aspirator above 160°F.

– Storage temperature: -51°C to +85°C (-60°F to +185°C).

– Interchangeability: This model is not compatible with other flame detector models.

Spare parts and accessories

124198: Mounting flange (aluminum) with 1″ NPT internal thread for mounting on the sighting pipe.

123539: Vibration-isolating support.

124204: Quartz focusing lens, nominal pressure 20 lbs/sq. inch (138 kPa); used to increase the sensitivity of the detector to ultraviolet radiation.

122748: Quartz viewing window; nominal pressure 50 psi. inch (345 kPa).

190105: Water jacket.

129464M: UV detector tube.

129464N: UV detector tube; designed for operation at temperatures up to -40°F (-40°C).

190971B: Coil and shutter.

114372: Quartz viewing window; nominal pressure 20 lbs/sq. inch (138 kPa).

114465: Gasket, silicone rubber; used to install the viewing window (requires three pieces).

120739: Gasket, fiber-neoprene; designed for thermal insulation and sealing of the mounting flange.

118367A: Rotary support.

118369: Bushing, galvanized steel, with an internal thread of NPT 3/4″ at one end and an external thread of NPT 1″ at the other end; used to install a detector with an internal thread of NPT 1″ on a sighting pipe with a 3/4″ thread or on a pipe nipple and tee for connecting the air supply.

120934: Mounting flange (aluminum) with 3/4″ NPT internal thread for mounting on the sighting pipe.