Flame detectors C7024E1001/U 24 V are solid-state electronic devices for measuring ultraviolet radiation emitted during the combustion of most carbon-containing fuels, such as natural gas, liquefied gas and oil.

Features

• Solid-state electronic circuit ensures low power consumption and high reliability.

• Detectors can be installed horizontally, vertically or at any intermediate angle. Self-monitoring models require alignment of the front panel and have built-in control points to ensure proper operation of the device.

• The tube for measuring ultraviolet radiation and the quartz viewing window are replaced in the field.

• Threaded pipe and color-coded lead wires ensure quick installation of electrical equipment.

• Two flame sensors can be connected in parallel to reduce the number of emergency shutdowns in complex flame detection systems.

• There is a swivel mount to facilitate the observation of the flame.

• Temperature -40° F (-40°C).

• Enables the UV sensor tube test function used in Honeywell R7824C devices.

• The oscillating shutter interrupts the UV radiation by accessing the UV sensor 12 times per minute to provide the UV sensor check function.

• The housing complies with NEMA 4 standards (indoor and outdoor protection: waterproof, dustproof, water supply from a hose).

• Protective heat block built into the mounting flange.

• High pressure (50 psi [345 kPa]) Quartz viewing window, focusing lens and anti-vibration mounting accessories are available.

Specifications

Flame detector: For use with dynamic self-monitoring R7824C amplifier.

Voltage: 24 V DC.

Power consumption: maximum 7.8 watts.

Rated ambient temperature (outside the enclosure): -20°F to +175°F (-29°C to +79°C).

Nominal storage temperature: -60°F to +175°F (-51°C to +79°C).

Nominal pressure of the quartz viewing window: 20 psi ([138 kPa). A focusing lens (20 psi [138 kPa] nominal) or a high pressure viewing window (50 psi [345 kPa] nominal) is available.

Mounting: Mounting flange with 3/4-inch NPT internal thread for mounting to the inspection tube.

Electrical connections: NEC Class 1 color-coded lead wires, 8 feet (2.4 meters) long.

Number of lead wires: 6.

Threaded lead wire hole in the front panel: 1/2-14 NPSM or 7/8-20 UNSM internal thread for fixing the pipeline.

Weight: Approximately 4.25 lbs (1.9 kg).

Easy maintenance: Replaceable viewing windows in the field and a tube for measuring ultraviolet radiation, a self-monitoring coil and a shutter assembly.

Spare parts

• 191286 UV sensitive tube for operation at -40°F (-40°C).

• 190971G Coil and gate assembly, 24 V DC.

• 114372 Quartz viewing window; designed for 20 psi (138 kPa).

• 114465 Silicone rubber gasket; to install the viewing window (requires three).

• 120739 Fiber neoprene gasket; thermal insulation and sealing of the mounting flange.

Accessories

• Measuring instrument W136A (includes a connector 196146 meter plug).

• 118367A Swivel mount.

• Quartz viewing window 122748, designed for 50 psi (345 kPa).

Brand