Honeywell SH213 mod.C1 03462C1 control box

SKU: 03462C1, 852.124.098

Price on request

3 People watching this product now!

Honeywell SH213 mod.C1 03462C1 control unit for liquid-fuel single-stage supercharged burners for pre-heating operation, with or without heating of liquid fuel.

Possible flame sensor:

  • MZ 770 S photoresistor
  • IRD 1010 infrared detector
  • UV flame sensor UVD 970

Satronic SH213 mod.C1 automatic gas firing device technical data:

  •  Maximum heating time of the fuel heater ta: 400 s
  • TV1 pre-ventilation time: 22 s
  • The opening signal of the door. during the pre-war. Ventilation TLK: 17 s
  • Air flap closing time tr: 5 s
  • Ambient light control TF: 10s
  • Safety time ts: 5 s
  • Time after ignition tn: 7 s
  • Delay terminal B/C tv2: 13 s
  • Operating voltage: 230 V (-15…+10%) 50/60 Hz (±5%)
  • Input fuse: 10 A high-speed, 6 A inert
  • Power consumption: approximately 12 VA
  • Air pressure switch: 1 working contact 4 A, 230 V
  • Sensitivity: 1.0 µA
  • Minimum required ionization current: 1.5 µA
  • Sensitivity to outside light: 0.4 µA
  • Wire length: < 3 m
  • Weight with base: 190 g
  • Installation position: any
  • Protection: IP 40
Brand