Honeywell SH213 mod.C1 03462C1 control unit for liquid-fuel single-stage supercharged burners for pre-heating operation, with or without heating of liquid fuel.
Possible flame sensor:
- MZ 770 S photoresistor
- IRD 1010 infrared detector
- UV flame sensor UVD 970
Satronic SH213 mod.C1 automatic gas firing device technical data:
- Maximum heating time of the fuel heater ta: 400 s
- TV1 pre-ventilation time: 22 s
- The opening signal of the door. during the pre-war. Ventilation TLK: 17 s
- Air flap closing time tr: 5 s
- Ambient light control TF: 10s
- Safety time ts: 5 s
- Time after ignition tn: 7 s
- Delay terminal B/C tv2: 13 s
- Operating voltage: 230 V (-15…+10%) 50/60 Hz (±5%)
- Input fuse: 10 A high-speed, 6 A inert
- Power consumption: approximately 12 VA
- Air pressure switch: 1 working contact 4 A, 230 V
- Sensitivity: 1.0 µA
- Minimum required ionization current: 1.5 µA
- Sensitivity to outside light: 0.4 µA
- Wire length: < 3 m
- Weight with base: 190 g
- Installation position: any
- Protection: IP 40