SKU: 0620920U, 534.412.902
Price on request
3 People watching this product now!
Satronic MMI810.1 mod.35 gas control unit designed for two-stage burners with forced draft, as well as for gas-oil combination burners.
Compatible flame detectors include:
- Ionization sensor
- Infrared flicker sensor
Honeywell MMI810.1 mod.35 control unit construction:
The automatic control system housed in a transparent, non-flammable plastic removable casing and includes:
- A synchronous motor with a speed reducer that drives the switching cam
- A switching cam equipped with a colorful display that shows the program status
- A 12-position cam mechanism to control the program sequence
- Plug-in printed circuit boards with electronic components
On the front panel of the control system, the following key indicators and control elements are located:
- A backlit button for fault indication and reset
- A colorful program display
- A central mounting screw
Resideo MMI810.1 mod.35 automatic gas firing device technical data:
- Waiting time at start-up: 9 s
- Max. reaction time for air proving switch: 6 s
- Pre-purge time: 24 s
- Pre-ignition time: 3 s
- T. ignition time: 8 s
- Safety time: 5 s
- Time delay term.6 / term.C: 10 s
- Operating voltage 220 / 240 V (-15… +10%) 50 Hz (50 – 60 Hz)
- Fuse rating: max. 10 A rapid, 6 A slow
- Power consumption: 10 VA
- Amplifier sensitivity: 1 µA
- Min. current from UV tube or ionisation probe: 5 µA
- Flame detector cable: max. 20 m cable length
- Air pressure monitor: working contact 4 A, 230 V
- Infrared flare detector: IRD 1020
- Weight incl. base: 350 g
- Mounting attitude: any
- Insulation standard: IP 44
- Permissable ambient temp.: -20° C… +60°C
- Classified acc. to EN 298: BTLLXN