Honeywell SG113 mod.C1 03502C1 control box

SKU: 03502C1, 852.124.087

Price on request

5 People watching this product now!

Satronic SG113 mod.C1 control box for gas and combined, two-stage or modulated supercharged burners.

Possible flame sensor:

  • Ionization probe
  • IRD 1020 infrared detector
  • UV flame sensor UVD 971

Resideo SG113 mod.C1 03502C1 control unit technical data:

  • Max. response time for TLW air pressure switch: 60 s
  • TV1 pre-ventilation time: 24 s
  • Time before setting fire to TVZ: 3 s
  • Time after ignition tn: 2 s
  • Stray light control TF: 5 s
  • Safety time ts: 3 s
  • Delay of the 2nd stage: 12.5 s
  • Operating voltage: 230 V (-15…+10%) 50/60 Hz (±5%)
  • Input fuse: 10 A high-speed, 6 A inert
  • Power consumption: approximately 12 VA
  • Air pressure switch: 1 working contact 4 A, 230 V
  • Sensitivity: 1.0 µA
  • Minimum required ionization current: 1.5 µA
  • Sensitivity to outside light: 0.4 µA
  • Wire length: < 3 m
  • Weight with base: 190 g
  • Installation position: any
  • Protection: IP 40