SKU: 03502C1, 852.124.087
Price on request
5 People watching this product now!
Satronic SG113 mod.C1 control box for gas and combined, two-stage or modulated supercharged burners.
Possible flame sensor:
- Ionization probe
- IRD 1020 infrared detector
- UV flame sensor UVD 971
Resideo SG113 mod.C1 03502C1 control unit technical data:
- Max. response time for TLW air pressure switch: 60 s
- TV1 pre-ventilation time: 24 s
- Time before setting fire to TVZ: 3 s
- Time after ignition tn: 2 s
- Stray light control TF: 5 s
- Safety time ts: 3 s
- Delay of the 2nd stage: 12.5 s
- Operating voltage: 230 V (-15…+10%) 50/60 Hz (±5%)
- Input fuse: 10 A high-speed, 6 A inert
- Power consumption: approximately 12 VA
- Air pressure switch: 1 working contact 4 A, 230 V
- Sensitivity: 1.0 µA
- Minimum required ionization current: 1.5 µA
- Sensitivity to outside light: 0.4 µA
- Wire length: < 3 m
- Weight with base: 190 g
- Installation position: any
- Protection: IP 40
Brand |
---|