Honeywell TF802.1 02404 control unit for 1- or 2-stage oil power burners up to 30kg/h capacity and intermittent operations.
Flame detection:
- Photoresistor FZ 771 S
- Infrared-flicker detector IRD 1010
- UV solid state sensor UVD 970
Satronic TF802.1 control box technical data:
- Delay time to oil valve 2: 40 sec
- Operating voltage 220/240 V (-15..+10%) 50 Hz (40-60Hz)
- Power consumption: ca. 5 VA
- Pre-purge time: ca. 12 sec
- Pre-ignition time: ca. 12 sec
- Post-ignition time: 2-4 sec
- Lockout safety time: 10 sec
- Reset time from lockout: ca. 90 sec
- Weight incl. wiring base: 0.25 kg
- Mounting position: any
- Protection class: IP44
- Recommended ambient operating temperature for control and flame detector: 0°C…+60°C