SKU: DWR6-313, 444.676.003
Price on request
4 People watching this product now!
Honeywell Fema DWR6-313 pressure switches designed for use with steam, hot water, fuel gases, and liquid fuels. Fema DWR6-313 differential pressure switches developed and certified for working with gases in accordance with DVGW G260 specifications and EN 1854 sealing standards. Honeywell DWR6-313 pressure switch can only be used within the electrical, hydraulic, and temperature ranges specified in the technical data table. The high-quality stainless steel components of the sensor, which come into contact with the working medium, allow Honeywell DWR6-313 differential pressure switch to be used in various environments. However, it is essential to conduct a chemical resistance test before selecting the device.
Honeywell Fema DWR6-313 pressure switch technical data
- Setting range: 0.2-6 bar
- Switching differential: 0.2 bar
- Maximum working pressure: 10 bar
- ambient temperature: -25 to 70 °C
- ambient temperature: 70 °C
- The difference in the sizes of materials operating at contact pressure (average values) when pulling the medium
- Switching: Single-pole switching
- Switching capacity: 8 (5) A, 250 V AC
- Installation position: Vertical and horizontal
- Pressure connection: External thread G 1/2” A (pressure gauge connection) according to DIN 16288 and internal thread G 1/4” according to ISO 228, Part 1. When working with gas, the internal thread is allowed only at pressures up to 4 bar. If the pressure is > 4 bar, use a flat O-ring.
Fema DWR6-313 differential pressure switch standards and directives
Standards:
- EN 13611
- DIN EN 1854
Directives:
- EU/2009/142/EC (GAD)
- EU/94/9/EC (ATEX)
Brand |
---|