Fema DWR16-206 pressure switch

SKU: DWR16-206, 444.676.021

Price on request

1 People watching this product now!

Honeywell Fema DWR16-206 pressure switches designed for steam, hot water, fuel gases, and liquid fuels. Honeywell DWR16-206 pressure switches developed and certified to operate with gases according to DVGW G260 specifications and EN 1854 sealing criteria. However, it is essential to conduct a chemical resistance test before selecting the device.

The standards include EN 13611 and DIN EN 1854, while the directives encompass EU/2009/142/EC (GAD) and EU/94/9/EC (ATEX).

Fema DWR16-206 pressure switch technical data

  • Setting range: 3-16 mbar
  • Switching differential: 75-3.15 mbar
  • Maximum working pressure: 20 mbar
  • ambient temperature: -25 to 70 °C
  • ambient temperature: 70 °C
  • The difference in the sizes of materials operating at contact pressure (average values) when pulling the medium
  • Switching: Single-pole switching
  • Switching capacity: 8 (5) A, 250 V AC
  • Installation position: Vertical and horizontal
  • Pressure connection: External thread G 1/2” A (pressure gauge connection) according to DIN 16288 and internal thread G 1/4” according to ISO 228, Part 1. When working with gas, the internal thread is allowed only at pressures up to 4 bar. If the pressure is > 4 bar, use a flat O-ring.
Brand