Honeywell Fema DGM506 pressure switches designed for use with steam, hot water, fuel gases, and liquid fuels. Fema DGM506 differential pressure switches developed and certified for working with gases in accordance with DVGW G260 specifications and EN 1854 sealing standards. Honeywell DGM506 pressure switch can only be used within the electrical, hydraulic, and temperature ranges specified in the technical data table. The high-quality stainless steel components of the sensor, which come into contact with the working medium, allow Honeywell DGM506 differential pressure switch to be used in various environments. However, it is essential to conduct a chemical resistance test before selecting the device.
Honeywell Fema DGM506 pressure switch technical data
- Setting range: 15-60 mbar
- Switching differential: 8 mbar
- Maximum working pressure: 5 bar
- ambient temperature: -25 to 60 °C
- ambient temperature: 60 °C
- The difference in the sizes of materials operating at contact pressure (average values) when pulling the medium
- Switching: Single-pole switching
- Switching capacity: 8 (5) A, 250 V AC
- Installation position: Vertical and horizontal
- Pressure connection: External thread G 1/2” A (pressure gauge connection) according to DIN 16288 and internal thread G 1/4” according to ISO 228, Part 1. When working with gas, the internal thread is allowed only at pressures up to 4 bar. If the pressure is > 4 bar, use a flat O-ring.
Fema DGM506 differential pressure switch standards and directives
Standards:
- EN 13611
- DIN EN 1854
Directives:
- EU/2009/142/EC (GAD)
- EU/94/9/EC (ATEX)
Brand |
---|