Fema DCM6 pressure switch

SKU: DCM6, 444.676.005

Price on request

5 People watching this product now!

Honeywell Fema DCM6 differential pressure switches designed to measure overpressure. Fema DCM6 gas pressure switches suitable for use in mechanical engineering, printing, pneumatics, and hydraulics. Honeywell DCM6 pressure switches calibrated for decreasing pressure, meaning the switching point on the scale corresponds to the moment the pressure drops, with the reset point being higher by the switching differential.

Fema DCM6 pressure switch technical data:

  • Setting range: 0.5-6 bar
  • Switching differential: 0.15 bar
  • Maximum working pressure: 16 bar
  • Pressure connection: External thread G 1/2 (pressure gauge connection) according to DIN 16 288 and internal thread G 1/4 according to ISO 228 Part 1
  • Switching device: Robust housing (200) made of seawater-resistant die cast aluminium GD Al Si 12
  • Degree of protection: IP 54, in vertical position
  • medium temperature: The maximum medium temperature at the pressure sensor must not exceed the permitted ambient temperature at the switching device. Temperatures may reach 85°C for short periods. Higher medium temperatures are possible provided the above limit values for the switching device are ensured by suitable measures (e.g. siphon)
  • Mounting: Directly on the pressure line (pressure gauge connection) or on a flat surface with two 4 mm Ø screws
  • Switching pressure: Adjustable from outside with screwdriver
  • Contact arrangement: Single-pole changeover switch
Brand