SKU: 37579000, 246.124.933
Price on request
1 People watching this product now!
Brahma DEN32 37579000 automatic controls units are designed to control atmospheric gas and liquid fuel burners in installations with an intermittent operating cycle.
Application
• Combination boilers
• Heating boilers
• Steam boilers
• Air heaters
• IR heaters
• Convectors
• Water heaters
• Furnaces
• Block burners
Certification
• EC certified (CE PIN 0694BP0610) in accordance with Directives 90/396 and 93/68 for gas appliances.
• Complies with EN 298 and EN 230:2005 standards for gas and liquid fuel systems and flame detectors.
Technical information
Supply voltage:
– Rated voltage: 220-240V, 50-60 Hz.
– Power consumption: 30 VA.
Performance characteristics:
– Temperature range: -20 °C – +70 °C.
– Maximum humidity: 95% at +40 °C.
– Protection: IP00.
Circuit breakers:
– Built-in fuse: 4 A.
– External fuse: 3.15 A.
Weight and dimensions:
– Maximum weight: about 200 g.
– Maximum length of external component cables:
– Room thermostat: 20 m.
– Remote alarm signal: 20 m.
– Ignition device (high voltage): 2 m.
– Other cables: 1 m.
Electrical connections:
– The installation must comply with national requirements and European electrical safety standards.
– Correct connection of phase and neutral is mandatory.
– The importance of grounding the controller and main power.
Timings:
– Pre-ventilation time (tv/tp): 10 sec
– Safety time (ts): 3 sec
Design
– Plastic housing to protect against mechanical damage, dust and dirt.
– Technology for surface mounting of electronic components to minimize dimensions.
– Varistor for protection against voltage surges in the power supply network.
Brand |
---|