SKU: 37542004, 246.124.241
Price on request
2 People watching this product now!
The Brahma NDM31 37542004 controllers are designed to control atmospheric gas and liquid fuel burners in installations with a non-constant operation cycle.
Brahma NDM31 37542004 gas control units have versions with both manual reset and electric: in the first case, the burner can be restarted only by pressing the reset button by the operator; in the second case, to restart the burner, it is necessary to disconnect and connect the main power supply.
Suitable for the following installations:
- Combined boilers
- Heating boilers
- Steam boilers
- Air heaters
- IR heaters
- Convectors
- Water heaters
- Furnaces
- Block burners
Specifications
• EC certificate (CE PIN 0694BP0610) in accordance with Directives 90/396 and 93/68 on gas equipment;
• Comply with EN 298 (European standard for gas systems and flame detectors);
• Comply with EN 230:2005 (European standard for liquid fuel systems and flame detectors);
• Two independent safety contacts for gas valve control;
• The ability to control Brahma valves of the VCM0x type;
• The ability to connect a custom module;
• Direct or pilot ignition.
Technical information
Rated supply voltage 220-240V, 50-60 Hz
Power Consumption: 30 VA
Temperature: -20 °C – +70 °C
Humidity: Max. 95% at +40 °C
Protection: IP00
Built-in fuse: 4 A
External fuse: 3.15 A
Maximum weight: about 200 g.
Maximum cable length of external components:
– Room thermostat: 20 m
– Remote alarm: 20 m
– Ignition device (high voltage): 2 m
– Other cables: 1 m
The presence of a base: no
Dimensions: 10.7×8.1×3.6 cm
Construction
1. Body Material: Made of plastic.
2. Protective functions: Protects the controller from mechanical damage, dust and dirt under operating conditions.
3. Production technology: Special technology for the production and surface installation of electronic components.
4. Compact: Allows you to keep the minimum dimensions of the controller.
5. Varistor: Protects the controller from power supply voltage fluctuations.
Electrical connections
• The installation must comply with national requirements and European standards (e.g. EN 60335-1/ EN 50165) for electrical safety;
• The phase and neutral must be connected correctly, an error can lead to dangerous situations. In case of non-compliance with the phase-neutral, the controller will operate in manual reset mode at the end of the start-up safety time;
• Check the cable connections carefully before starting the system. An incorrect connection can damage the controller and compromise security;
• Check the grounding of the controller, the metal housing of the burner and the grounding of the main power supply;
• Ensure the distance between the ionization cable and the power cables/ignition cables;
• Use the shortest and straightest ignition cable possible (max length 25kV).
Brand |
---|