SKU: 37201260, 246.124.160
Price on request
4 People watching this product now!
Brahma MPI 37201260 control unit – control of burners with forced draft, mixed fuel. New product, one control unit, non-volatile locking, air flap control. It is suitable for multistage and modulating burners in domestic and industrial heating.
General characteristics
• Flame control using flame straightening (ionization) properties or UV1 type ultraviolet phototubes (technical specifications are specified in the relevant technical data sheets).
• Two independent safety contacts for controlling the gas valve.
• The service life of electrical equipment is more than 250,000 operations at the maximum declared load.
• Built-in and/or remote manual reset with liquid crystal indication of the reasons leading to an emergency shutdown.
• The ability to control the valve inspection system at the pre-purge stage or after purging.
• Easy to install and connect.
• The possibility of multiple ignition attempts depending on the end use.
• Operating cycles compatible with the LFL1 type controller (Siemens). When replacing the control unit, the outlet must also be replaced.
Technical specifications
Power supply: 230 V (+10%/-15%) – 50/ 60 Hz; on request: 110/120 V (+10%/-15%) – 50/ 60 Hz
Operating temperature range: -20°C + 60°C
Ambient humidity: no more than 95%
Degree of protection: IP40
Classification codes:
according to EN 298:03 FBLLXN
according to EN 230:05 FTLLXN ”WLE”
Power consumption at startup: 7.5 VA
Power consumption during operation: 9 VA
The presence of a base: no
Pre-ventilation time (TV/tp): 36 sec
Safety time (ts): 2 sec
Tightness control of gas valves: yes
Weight: 0.95 kg
Dimensions: 10.3×10.3×9.1 cm
Construction
The use of SMT technology and a special plastic housing provide flexibility in controlling the air flap and protection from damage caused by accidents, careless handling, dust and dirt. The built-in varistor prevents damage during power surges. A fuse inside the Brahma MPI 37201260 control unit protects the control relay from short circuits at the outputs (gas valves, motor, transformer, lock signal). It is also recommended to use an external fuse up to 6.3 A for additional protection.