SKU: 37030015, 246.124.168
Price on request
4 People watching this product now!
Specially designed for intermittent cycle atmospheric burners, Brahma FM31 37030015 ignition automatics are suitable for a variety of applications:
• combined boilers;
• heating systems;
• air heaters;
• IR heaters;
• water heaters.
Flame control in these controllers is based on the ionization effect, while a high voltage is present on the control electrode, which makes it inaccessible to safe touch.
Specifications
– EC certificate (CE Reg. N°0694BP0669) in accordance with Directives 90/396 and 93/68 on gas equipment;
– Ionization control of the flame;
– Two independent safety contacts for controlling the gas valve;
– Built-in high-efficiency ignition device;
– Single flame;
– An atmospheric burner with a fan;
– Classification code according to EN 298: AMCLXN.
Supply voltage: 220/240V – 50/60Hz
On request: 110/120V – 50/60Hz
Temperature: -20 ℃ – +60 ℃
Humidity: Max. 95% at 40℃
Protection: IP 00
The presence of a base: no
Time:
– Pre-ventilation time (tv/tp):5 seconds
– Safety time (ts):10 sec
– Waiting time (tw):5 seconds
Minimum ionization current:1.2 mA
Max. cable length of external components: 1m
Built-in fuse: 3.15 A
External fuse: 2 A
Ignition device
– Voltage: 20 kV
– Frequency: 25 Hz
– Max. Cable length: 2 m
– Spark distance: 2-4mm
– Power Consumption: 2.5 VA
– Spark: 15 MJ
Weight: 170 gr.
Dimensions:13×7.5×3.6 cm
Construction
– Protection from external influences:
– The housing made of plastic serves as an effective barrier that protects the Brahma FM31 37030015 burner control unit from mechanical damage, dust and dirt under operating conditions.
– Protection against voltage surges:
– The presence of a varistor in the controller design provides reliable protection against voltage fluctuations in the power supply network, maintaining the stability of the device.
– Optimized dimensions:
– The use of special production technology and surface installation of electronic components allows you to achieve the minimum overall dimensions of the control unit, ensuring compactness and ease of installation.
Operation of the controller
– Self-checking of components:
– The Brahma FM31 37030015 relay checks the flame signal amplifier and, if there is a fan, the air pressure switch at each start.
– Sequential start-up:
– Upon successful self-check, a sequential start begins, including purging, activation of the gas valve (VG1), ignition, safety countdown (TS) and flame detection check.
– Activation of devices upon flame detection:
– In case of successful flame detection, all necessary devices, including the VG1 gas valve, are activated, ensuring stable operation of the system.
– Manual locking in the absence of flame:
– If no flame is detected after the safety time (TS), the controller switches to manual lock mode, turning off the VG1 gas valve and the ignition device.
– Detailed cyclograms:
– Additional information about the functions of the controller is provided in the cyclograms, providing a more detailed understanding of the work processes.
Reset the lock
When switching to lock mode, the lock must be reset no earlier than 10 seconds later; otherwise, the controller may restart incorrectly.
Brand |
---|