Brahma SM592.2 36283301 controllers are designed to work with atmospheric gas burners and for burners with a fan, with non-constant (intermittent) operation mode.

All automatic ignition Brahma SM592.2 36283301 manual reset: restart the installation by pressing the RESET button.

Certificates and standards

• Certificate (CE Reg. N° 51BT3691) in accordance with Directives 90/396 and 93/68;

• Compliance with EN 298:2003 (European Standard for gas burner control systems.

Technical information

Power Supply: 230V – 50/60Hz

Operating temperature: -20 degrees to +60 degrees

Humidity: max. 95% at 40 degrees

Protection: IP 40

Time:

– Purge (TW) 1.5 sec

– Safety (TS): 5 seconds

– Flame loss response: < 1 sec

Power consumption, at startup: 20 VA

Energy consumption during operation: 14 VA

Flame control:

– Minimum ionization current:1.2 mA

– Recommended ionization current: 3-5 times more min. ionization current

– Max. cable length: 1 m.

Weight with the pad: 275g.

Dimensions: 8.5×6.8×6.5 cm

Installation and electrical connection recommendations

1. Restarting the system is recommended every 24 hours for technical and safety reasons (for systems with non-permanent gorenje).

2. Connect and disconnect the controller only when the power supply is turned off.

3. The controller can be installed in any position.

4. Avoid getting water droplets on the controller.

5. Ensure proper ventilation and maintain an optimal temperature to extend the life of the controller.

6. Before installing or replacing the controller, make sure that its type and time characteristics are correct.

Basic provisions on electrical connection

1. Make sure that the installation complies with national requirements and European standards for electrical safety, such as EN 60335/1prEN 50165.

2. The correct connection of the phase and neutral is necessary to avoid dangerous situations. In case of an error, the controller will switch to manual reset mode after the set start-up safety time is completed.

3. Before starting the system, carefully check the cable connections to avoid damage to the controller and ensure safety.

4. Check that the controller, the metal body of the burner and the main power supply are grounded.

5. Ensure the necessary distance between the ionization cable and the power/ignition cables.

6. Use a well-insulated ionization electrode, protected from moisture and humidity.