Brahma 36223331 SM592N/S control box

SKU: 36223331, 246.124.178

Price on request

2 People watching this product now!

Brahma SM592N/S 36223331 control box are designed to work with atmospheric gas burners and burners with a fan operating in intermittent operation mode. It is important to note that all ignition automation mechanisms, including manual reset devices, are designed so that the system is restarted by pressing the RESET button.

Certificates and standards:

– Certificate (CE Reg. N° 51BT3691) with compliance with directives 90/396 and 93/68;

– Compliance with EN 298:2003 (European Standard for gas burner control systems).

Technical information:

– Power supply: 230V – 50/60Hz.

– Operating temperature: -20 degrees to +60 degrees.

– Humidity: max. 95% at 40 degrees.

– Protection: IP 40.

Time parameters:

– Purge (TW): 1.5 sec.

– Safety (TS): 5 sec.

– Pre-ventilation time (tv/tp):1.5 sec

– Flame loss response: < 1 sec.

Energy consumption:

– At startup: 20 VA.

– In operation mode: 14 VA.

Flame control:

– Min. Ionization current: 0.5 mA.

– Recommended ionization current: 3-5 times more min. the ionization current.

– Max. cable length: 1 m.

Dimensions and weight:

– Weight with pad: 275 g.

– Dimensions: 8.5×6.8×6.5 cm.

Installation Recommendations:

Restart the system regularly every 24 hours to ensure safety and efficient operation. Connect and disconnect the controller when the power supply is off to avoid damage. You can install the Brahma SM592N/S 36223331 burner control unit in any position for convenience. Avoid getting water on the controller to prevent damage. Ensure proper ventilation and maintain an optimal temperature for durability. Before installing or replacing the Brahma SM592N/S 36223331 automatic gas firing devices, check its compliance with the type and characteristics of the time.

Electrical connection:

Comply with national requirements and safety standards such as EN 60335/1prEN 50165. Proper phase connection is required to avoid dangerous situations. Before starting the system, carefully check the cable connections to prevent damage. Check the grounding of the controller, the metal housing of the burner and the main power supply. Keep the required distance between the ionization cable and the power/ignition cables. Use an ionization electrode with good thermal insulation, protected from moisture to ensure safety.

Checking at startup:

Perform a mandatory check of the Brahma SM592N/S 36223331 relay before the first power-on and in case of changes in the installation or prolonged downtime of the system.

Lock reset:

In case of switching to emergency mode, the reset should be carried out no earlier than 10 seconds, providing the necessary delay to prevent accidental or unwanted resets in emergency situations.