Brahma 20657621 CE191.4 control box

SKU: 20657621, 246.124.203

Price on request

5 People watching this product now!

Brahma CE191.4 20657621 controllers – efficient control of gas burners with a fan, capable of operating independently of combustion in the circuit.

Features

• Flame control based on the rectifying properties of the flame (ionization);

• Two independent safety contacts in series at the outlet of the gas valve (models with manual reset);

• Service life of electrical equipment at max. declared load > 250,000 operations;

• Built-in fully solid-state ignition device with high efficiency;

• EU certification type (CE PIN code 0694BR1154) in accordance with Directive 90/396 on gas appliances and the following amendment to Directive 93/68;

• In accordance with EN 298 (European standard for automatic programming and flame control systems for gas burners);

• Auxiliary contact for low-power ignition or control of the main gas valve in intermittent power control systems (this contact is not isolated from the main supply voltage by reinforced insulation, therefore the relay contact is not suitable for controlling SELV circuits

Technical specifications

Power supply: 230 V – 50/60 Hz; on request: 110-120 V – 50/60 Hz

Operating temperature range: -20 °C +60 °C

Humidity: max. 95 % at 40 °C

Degree of protection: IP00

Pre-ventilation time (TV/tp): 10 seconds

Safety time (ts): 10 sec

Standby Time (tw): 10 sec

Response time in case of flame failure: ≤ 1 s

Minimum ionization current: 1.2 µA

On request: 0.5 µA

Recommended ionization current: 3-5 times the minimum ionization current

Maximum cable length: 1m

Maximum parasitic electrode capacitance: ≤ 1 NF

Maximum short-circuit current: < 200mA AC

Maximum ionization current (230 V 50 Hz): 8 µA DC

Ignition voltage: 20 kV at 30 pF load

Spark repetition rate: 25 Hz

Maximum cable length: 2 m

Recommended discharge distance: 2-4mm

Power consumption: 2.5 VA

Spark energy: 15 MJ

Weight: 200 g

Construction

– Durable plastic housing and self-extinguishing material.

– Optimized dimensions thanks to the module with electronic components on the surface.

The principle of operation

– Self-monitoring when switching on, including checking the flame signal amplifier and the air pressure switch.

– Blocking when faults are detected, ensuring the safety of the system.

Brand