Brahma 18049105 GR2 control box

SKU: 18049105, 246.124.025

Price on request

4 People watching this product now!

Brahma GR2 18049105 gas control unit is designed to automate the start and control of all functions of liquid fuel burners with air supply to the furnace. Brahma GR2 18049105 relay provides continuous monitoring of the flame gorenje, disabling the safe shutdown of fuel supply in case of failures. The exit from the lock state is carried out easily by pressing the reset button or via a remote device, which ensures ease of operation and reliability of operation.

Technical data:

– Automation resource: more than 250 thousand switching cycles at maximum loads.

– Supply voltage: 220÷240 V∼ at 50/60 Hz; on request: 110÷120 V∼ at 50/60 Hz.

– Operating temperature range: -20°C ÷ +60°C.

– Ambient humidity: no more than 95% at a temperature of 40 °C.

– Degree of protection: IP 40.

Timings:

– Pre-purge time (TV): 10 s.

– Safe time (TS): 10 sec.

– Dropout time when the working flame is turned off: < 1 s.

Power consumption:

– At a supply voltage of 220÷240 V AC: 8 VA.

– At a supply voltage of 110÷120 V AC: 4 VA.

Maximum cable length of external components:

– Thermostats (T – TC): 20 m.

– Reset and alarm (RE – SB): 10 m.

– All others: 1 m.

Shutdown voltage:

– For supply voltage 220÷240 V AC: 85 V AC.

– For supply voltage 110÷120 V AC: 45 V AC.

– Internal fuse power: 6.3 A with delay.

– Power of the external fuse: 6.3 A with fast operation.

Additional features:

– Weight (including socket): 132 g

. – Operating temperature: -10 ÷ +60°C.

– Burner capacity: up to 30 kg/hour.

– Dimensions: 8.5×6.9×6.5 cm.

Features:

– Double flame.

– Preheater (possible).

– Built-in reset.

– Flame sensors FC11/ FC13/ FC14/ FC14L/.

– Flame sensors FT11/ FT13/.

Construction:

1. Unique design: The use of surface-mounted components reduces the overall dimensions of the control panel.

2. Plastic housing: Provides protection against damage such as collisions, careless opening, dust ingress, as well as contact with the external environment, providing additional durability and safety of the device.

3. Varistor: The inclusion of a varistor in the design protects the control system from sudden voltage surges in the electrical network, ensuring stable and safe operation of the control unit.

4. Built-in fuse: Provides additional protection for the internal relays of the control unit in the event of a short circuit at the outputs, such as valves, ignition transformer, motor and lock signal.

These security measures contribute to:

– Reliable and long-term operation of the control system.

– Stability in various operating conditions.

Brand