The Brahma GR1 18049099 automatic control box is designed specifically for single-stage supercharged liquid fuel burners with variable operating mode. Brahma GR1 18049099 relay provides control and management of the fuel combustion process, guaranteeing the safety of operation of the entire system.
Technical data
– The resource of automation is more than 250 thousand cycles of switching on at maximum loads.
– Supply voltage: 220÷240 V∼ at 50/60 Hz; on request: 110÷120 V∼ at 50/60 Hz
– Operating temperature range: -20°C ÷ +60°C
– Ambient humidity: no more than 95% at 40°C
– Degree of protection: IP 40
Timings:
– Pre-purge time (TV): 10 s
– Safe Time (TS): 10 s
– Dropout time when the working flame is turned off: < 1 s
Power consumption:
– at a supply voltage of 220÷240 V AC: 8 VA
– at a supply voltage of 110÷120 V AC: 4 VA
Maximum cable length of external components:
– Thermostats (T – TC): 20 m
– Reset and alarm (RE – SB): 10m
– Everyone else: 1 m
Shutdown voltage:
– for supply voltage 220÷240 V AC: 85 V AC
– for 110÷120 V AC supply voltage: 45 V AC
– Internal fuse power: 6.3A with delay
– Power of the external fuse: 6.3 A with fast operation
– Weight (including socket): 132 g
– Operating temperature: -10 ÷ +60°C.
– Burner capacity – up to 30 kg/h.
– Continuous flame monitoring by FC11, FC13, FC14 or FC14L photodetector;
– Dimensions: 8.5×6.9×6.5 cm
Construction
The unique design and the use of surface-mounted components make it possible to reduce the overall dimensions of the control panel. The plastic case provides protection against damage, such as collisions, careless opening, dust ingress, as well as contact with the external environment, providing additional strength and safety of the device.
The inclusion of a varistor in the design protects the control system from sudden voltage surges in the electrical network, which contributes to the stable and safe operation of the control unit. The built-in fuse provides additional protection for the internal relays of the control unit in the event of a short circuit at the outputs, such as valves, ignition transformer, engine and lock signal. These safety measures contribute to the reliable and long-term operation of the control system in various operating conditions.
Connection
For convenient and safe connection of external components, the control unit can be equipped with a type N connector providing a screw terminal block. This ensures simplicity and security when connecting. It is recommended to use M4 type screws to secure the sockets securely. To secure the control element to the outlet, use the pin included in the control unit package. These recommendations ensure ease of installation and ensure reliable connection of external components to the control unit.
Brand |
---|