Brahma 18048700 GR1 control box

SKU: 18048700, 246.124.164

Price on request

5 People watching this product now!

The Brahma GR1 18048700 burner control units are designed specifically for oil burners designed for intermittent operation. These automatic burner control units of the Brahma GR1 18048700 series are suitable for a variety of applications, including monoblock oil burners, electric washing machines, warm air generators, steam boilers and furnaces.

Due to their technical and design characteristics, as well as a variety of models, these Brahma GR1 18048700 burner control units can be successfully used to automate various devices with oil burners, including kitchen stoves and appliances for both domestic and industrial purposes.

It is assumed that these units provide efficient and reliable control of the oil combustion process in the burner, which makes them suitable for a wide range of applications where automation of oil burners in variable operating conditions is required.

Features

Features of Brahma GR1 18048700 controllers:

– Designed for non-permanent operation.

– Operate at a fuel consumption of less than 30 kg/h (TSMAX = 10 s) or a fuel consumption of 30 to 100 kg/h (TVmin = 15 s and TSMAX = 5 s).

– Comply with DIN EN 13842:2004-10 standard for warm air generators (WLE) in versions with TV = 20 s and TS = 5 s.

– Have two independent safety contacts for controlling the oil valve.

– The service life of electrical equipment at maximum load exceeds 250,000 operations.

– Single flame mode is supported.

– Preheater installation is possible.

– There is a built-in reset function.

– The possibility of an external remote reset is provided.

– Flame sensors FC11/, FC13/, FC14/, FC14L/, FT11/, FT13/ are supported.

These features make Gorenje Brahma GR1 18048700 combustion control units versatile and suitable for various applications where efficient and reliable control of oil burners is required during variable operation. Compliance with standards and the availability of additional functions, such as a preheater and an external remote reset, expand their functionality and ensure compliance with modern safety and efficiency requirements.

Technical data

Supply voltage: 220÷240 V∼ at 50/60 Hz; on request: 110÷120 V∼ at 50/60 Hz

Operating temperature range: -20°C ÷ +60°C

Ambient humidity: no more than 95% at 40°C

Degree of protection: IP 40

Timings:

– Pre-purge time (TV): 10 s

– Safe Time (TS): 10 s

– Dropout time when the working flame is turned off: < 1 s

Power consumption:

– at a supply voltage of 220÷240 V AC: 8 VA

– at a supply voltage of 110÷120 V AC: 4 VA

Maximum cable length of external components:

– Thermostats (T – TC): 20 m

– Reset and alarm (RE – SB): 10m

– Everyone else: 1 m

Shutdown voltage:

– for supply voltage 220÷240 V AC: 85 V AC

– for 110÷120 V AC supply voltage: 45 V AC

– Internal fuse power: 6.3A with delay

– Power of the external fuse: 6.3 A with fast operation

– Weight (including socket): 132 g

– Operating temperature: -10 ÷ +60°C.

– Burner capacity – up to 30 kg/hour.

Construction

The special design and use of components installed on the surface make it possible to reduce the overall dimensions. The case, made of plastic, protects the control panel from possible damage as a result of collisions, careless opening, dust ingress and contact with the external environment. The varistor protects the control system from voltage surges in the electrical network. The built-in fuse protects the internal relays of the control unit in case of a short circuit at the outputs (valves, ignition transformer, engine and lock signal).

Connection

To connect external components, the control unit can be equipped with an N-type connector equipped with a screw terminal block, which provides a simple and safe connection. It is recommended to use M4 type screws to attach the sockets. To attach the control element to the outlet, use the pin included in the control unit package.