The Brahma TGRD63 18047002 burner controllers based on KOMPACT series microcontrollers are specially designed for controlling gas atmospheric burners (with or without a fan in the combustion circuit) or oil atmospheric burners in non-constant operation conditions. The KOMPACT series of the TGRD type was created due to the need for an ignition and flame control device with a built-in high-efficiency electronic ignition transformer (a function already available in the KOMPACT series of the TGR type) with all the options and flexibility offered by a single microcontroller technology. These systems are equipped with a non-volatile or energy-dependent lock, in the first case, restarting the controller from the protective lock state can only be performed by manually resetting the system, and in the second case, restarting the controller from the protective lock state can only be achieved by interrupting the power supply and its subsequent restoration (and not by switching the heating device).

Application

Brahma TGRD63 18047002 gas burner control box are suitable for:

– Combined, heating and steam boilers; – Hot air generators; – radiation tubular heaters;

– convector heater with fan;

– Water heater;

– washing machine;

– furnaces;

– Monoblock burners.

Brahma TGRD63 18047002 automatic gas firing device is suitable for use in gas hot air generators in accordance with EN 525, EN 1020 and EN 1319 standards or in oil hot air generators in accordance with Part 2 of DIN 4794 standard.

Technical data

• Rated supply voltage: 200÷240V @ 50-60 Hz

• On demand: 100÷120V @ 50-60 Hz

• Maximum power consumption: 50V

• Operating temperature: -20 °C ÷ +70 °C

• Protection: IP00

• Max. Weight: 320g

• Standby/pre-purge time (TW/TP): 1 … 120 s

• Safety Time (TS): 3 … 120 s

• Reaction time when the flame disappears: < 1 s

• Waiting time or industrial purge: s 1 … 240 s

• EV2 opening delay (Tdw, opt. W): 1 … 240 s

• Blocking delay due to flame simulation(Tdk, opt. K): 0 … 60 s

• Blocking in case of failure to close the PA (Tdq, opt. Q): 3 … 120 s

• Blocking in case of failure to close TC (Tdq, opt. Q) (7): 3 s … 30’

• Pre-ignition time(Tj, opt. J): 0 … 60 s

• Attempts to restart: 1 … 10

• Lacquer coating: On demand

Constructive

The use of an innovative circuit and components for surface mounting made it possible to reduce the dimensions of the controller circuit board.

The plastic housing (and the lacquer coating on the printed circuit board, if required) protect the controller from mechanical damage caused by an accident, hardening, dust and contact with the external environment.

The varistor protects the controller from peak voltage in the power grid caused, for example, by atmospheric discharges, such as lightning strikes.

An internal available fuse protects the controller relay in the event of a short circuit at the outputs (valves, fan and lock signal).

The built-in electromagnetic interference filter reduces electromagnetic interference generated by the ignition discharge.

Finally, a resistor connected in series to the lock output signal can be installed to protect the device from possible inversions of the remote unlock contact connection.

Functions

• EU type certification (CE PIN 0694BP0610) in accordance with the Gas Appliances Directive 2009/142/CE.

• Compliance with the standards EN298:2003 (automatic gas burner control systems), EN676:2003 (automatic supercharged gas burners), DIN 4788 (burners with fan) and EN230:2005 (automatic oil burner control systems).

• UL type certification (file no. MH46742) in accordance with UL 372 and CSA C22.2 No. 199 (American Standard for Automatic Control Systems for Gas and Liquid Fuel Stoves).

• Flame detection based on rectification properties (electrode or UV radiation via FD photodiode.. for gas emissions) or detection of the appearance of visible light (through a photocell of type FC.. or UV radiation through the FD photodiode.. for oil emissions).

• Using microcontroller technology to accurately set ignition timing and playback with or without multiple attempts.

• Built-in electronic ignition transformer with high efficiency and remote control.

• The possibility of direct ignition of the burners or the use of an intermittent or intermittent pilot signal.

• Support for connecting remote signals, locking and resetting.

• Indication of the status of the lock and unlock signals using a multi-color LED on the board.

• Two safety contacts for controlling the gas valve.

• The service life of the electrical resource at high temperatures is more than 250,000 operations.

• The possibility of connecting a resistor (100 ÷ 470 kOhm) to the signal blocking output to prevent damage to the controller in case of accidental entanglement of the blocking wires and blocking signal wires.