Brahma 15911360 TD2STCS ignition transformer

SKU: 15911360, 246.820.123

Price on request

3 People watching this product now!

BRAHMA TD2STCS 15911360 ignition transformers are used in gas burners, burners for light and heavy types of liquid fuels in both domestic and commercial and industrial installations.

Specifications

  • Single or double-pin high voltage output;
  • Various mounting and connecting systems;
  • Built-in short circuit protection;
  • The possibility of delivery with an integrated EMC filter;
  • 100% duty cycle;
  • Light weight and compact size;
  • High efficiency and ignition power;
  • Low power consumption;
  • In gas and liquid fuel burners, the safety of ignition transformers depends on the controller.

Technical information

Number of contacts: 2

Peak output voltage kV: 12*2

Peak current mA: 55

kHz output voltage frequency (1): 8.5

kHz output voltage frequency (2): 12

VA Energy Consumption: 30

Supply voltage: 220-240 V 50/60 Hz On request: 110-120 V 50/60 Hz

Operating temperature: -10 … +60 °C

Protection: IP00

Recommended electrode spacing (spark distance): 3-5 mm

Max. length of ignition cable: 1.5 m

Standard power cable length: 560mm

Weight: about 360 g.

Construction

1. The principle of operation with a high-frequency electronic generator ensures compactness and light weight with high ignition power.

2. The electronic circuit and the ferritic transformer are processed to protect against temperature fluctuations and overloads.

3. The built-in varistor protects the device from power surges in the network.

4. Available in various versions: with different number of contacts, types of high voltage connections and cable, with/without electromagnetic filter.

Connections

1. BRAHMA TD2STCS 15911360 transformers with ignition cable are compatible with Brahma controllers and are installed on the transformer using M4x45 screws.

2. Transformers are offered with a built-in power cable or connector for it, providing flexibility in installation.

3. The connection of the high-voltage cable is carried out inside the insulator and is available in two versions: threaded connection or connection with a connector ø4 mm.

4. All connectors, including connectors with cable, are available on request.

Installation

  • ATTENTION! HIGH VOLTAGE.
  • Connect and disconnect the BRAHMA TD2STCS 15911360 transformer only after the power is turned off.
  • The installation is carried out in accordance with national and European standards (e.g. EN60355-1 / EN50165) for electrical safety.
  • The installation must ensure that the valve body is connected to the ground to provide protection against electric shock (EN60335-1).
  • The transformer is installed in any position.
  • Do not place high-voltage cables next to other cables.
  • Ensure the appropriate level of protection for this installation.