Brahma 13924740 EG15*L*GMO gas valve

SKU: 13924740, 246.322.037

Price on request

1 People watching this product now!

BRAHMA EG15*L*GMO 13924740 gas solenoid valves have a normally closed type, are suitable for civil and industrial applications, are powered by alternating or direct current and are equipped with a mesh filter at the inlet, preventing dirt from entering with a thickness of more than 1 mm.

Installation options

It is possible to install a BRAHMA EG15*L*GMO 13924740 quick-opening valve or a slow-opening valve (obtained using a special hydraulic shock absorber) with flow control and an initial flow of quick-opening adjustment and pressure plugs at the inlet and outlet.

Standards and certification

BRAHMA EG15*L*GMO 13924740 gas valves conforming to the EN 161 standard have a CE type certificate (CE registration number 63AQ0626) in accordance with European Directives 90/396 and 93/68.

Technical specifications

Class: A

Group: 2

Supply voltage (1): 220-240 VAC / 50-60 Hz

Operating temperature: -10°C / +60°C

Closing time: 1 s

Opening time: 1 sec

Installation: vertical and horizontal

Body: die-cast aluminum

Core mounting: PG9

Working pressure: 500 mbar

Hole diameter: 15mm

Weight: 850 g

Voltage: 22 VA

Gas flow: 8 m3/h

Opening type: The valve opens slowly and silently (this version has a flow regulator)

Connection type: Connection to the terminal block-IP40

Winding type: The power is supplied by alternating current, but the valve operates on direct current due to the built-in rectifier bridge

Flow adjustment

To adjust the gas flow rate, unscrew one of the two screws used to attach the flag group and turn the entire group clockwise to reduce the flow, or in the opposite direction to increase it.

Adjusting the opening time

After removing the upper protection, turning it counterclockwise, it is necessary to press the adjusting screw; when rotating clockwise, the opening time increases, when rotating in the opposite direction, the opening time decreases.

Quick-release initial flow adjustment

After removing the upper guard by turning it counterclockwise, if you turn the nut clockwise, the initial release will be reduced; if you turn the same nut counterclockwise, the initial release will be increased.

Installation

  • Comply with applicable national and European standards (e.g. EN60335-1) regarding electrical safety.
  • Install the BRAHMA EG15*L*GMO 13924740 valve at the installation location so that the arrow on the valve body has the same direction as the fuel flow.
  • When mounting the valve to the mounting pipe, avoid twisting the casing and always use a hex wrench to attach it to the valve body.
  • Make sure that there are no foreign objects inserted into the valve body.
  • Make sure that the max. fuel inlet pressure never exceeds the values mentioned on the label.