Brahma E6G*L*1/2*GFDF8 13782100 gas control blocks are normally closed, used in domestic and industrial installations, operate on direct and alternating current. They are divided into two groups: with a nozzle diameter of 8 or 10 mm.
Brahma E6G*L*1/2*GFDF8 13782100 gas solenoid valves comply with EN161, have a CE certificate (Reg. N° 63AQ0626) in accordance with European Directives 90/396 and 93/68.
Technical specifications
Valve class: A
Supply voltage: 230 V / 50-60 Hz
Operating temperature: -10°C / +60°
Closing time: 1sec
Opening time: 1sec (for versions with fast opening)
Installation: Vertical and horizontal
Body Material: Brass
Working pressure: 0-200 mbar
Nozzle diameter: 10 mm
Weight: 850 g
Consumption: 20 VA
Natural gas consumption: 3.9 m3/h
Pressure sampling control point: +
Connection type: Quick-release connection for DIN43650 – IP65 (GFD IP40)
Opening type: Slow opening, silent. With expense settings
Installation
- The installation is carried out in accordance with national and European standards (e.g. EN 60335-1) for electrical safety.
- Install the Brahma E6G*L*1/2*GFDF8 13782100 gas control unit so that the arrow on the valve body coincides with the flow direction.
- During the installation of the Brahma E6G*L*1/2*GFDF8 13782100 gas valve on the pipeline, avoid displacement of the protective shell and always use a hex key of the appropriate size.
- Make sure that no foreign objects have entered the valve.
- Make sure that the inlet pressure of the Brahma E6G*L*1/2*GFDF8 13782100 gas solenoid valve does not exceed the pressure indicated on the valve.
Setting up the flow rate
To adjust the flow rate of the valve, unscrew 1 of the 2 mounting screws of the hydraulic brake unit and rotate the entire hydraulic brake unit clockwise to reduce flow or counterclockwise to increase gas flow through the Brahma E6G*L*1/2*GFDF8 13782100 compact gas unit.
Setting the opening time
Remove the upper protective plug by rotating it counterclockwise. Rotate the adjustment screw: clockwise to increase the opening time of the Brahma E6G*L*1/2*GFDF8 13782100 gas valve, counterclockwise to decrease the opening time of the valve.
Setting up a quick opening of the initial stream
Remove the protective plug by rotating it counterclockwise. Rotate the adjusting nut: clockwise to reduce the initial flow, counterclockwise to increase the initial flow.