Brahma 13775001 E6G*L*3/8*GMO gas valve

SKU: 13775001, 246.322.092

Price on request

2 People watching this product now!

Brahma E6G*L*3/8*GMO 13775001 gas control blocks are normally closed, used in domestic and industrial installations, operate on direct and alternating current. They are divided into two groups: with a nozzle diameter of 8 or 10 mm.

Brahma E6G*L*3/8*GMO 13775001 gas solenoid valves comply with EN161, have a CE certificate (Reg. N° 63AQ0626) in accordance with European Directives 90/396 and 93/68.

Technical specifications

Valve class: A

Supply voltage: 230 V / 50-60 Hz

Operating temperature: -10°C / +60°

Closing time: 1sec

Opening time: 1sec (for versions with fast opening)

Installation: Vertical and horizontal

Body Material: Brass

Working pressure: 0-200 mbar

Nozzle diameter: 10 mm

Weight: 850 g

Consumption: 20 VA

Natural gas consumption: 3.9 m3/h

Pressure sampling control point: +

Power supply type: Alternating current, but the valve is controlled by a DC signal due to the built-in bridge rectifier circuit

Connection type: Terminal block connection – IP54

Opening type: Slow opening, silent. With expense settings

Installation

  • The installation is carried out in accordance with national and European standards (e.g. EN 60335-1) for electrical safety.
  • Install the Brahma E6G*L*3/8*GMO 13775001 compact gas unit so that the arrow on the valve body coincides with the flow direction.
  • During the installation of the Brahma E6G*L*3/8*GMO 13775001 gas valve on the pipeline, avoid displacement of the protective shell and always use a hex key of the appropriate size.
  • Make sure that no foreign objects have entered the valve.
  • Make sure that the inlet pressure of the Brahma E6G*L*3/8*GMO 13775001 gas solenoid valve does not exceed the pressure indicated on the valve.

Setting up the flow rate

To adjust the flow rate of the valve, unscrew one of the two mounting screws of the hydraulic brake unit and rotate the entire hydraulic brake unit clockwise to reduce flow, or counterclockwise to increase gas flow through the Brahma E6G*L*3/8*GMO 13775001 valve.

Setting the opening time

Please remove the upper protective cover by turning it in the opposite direction clockwise. Adjust the adjustment screw: rotate clockwise to increase the opening time of the Brahma E6G*L*3/8*GMO 13775001 gas valve and counterclockwise to decrease it.

Setting up a quick opening of the initial stream

To remove the protective plug, turn it counterclockwise. Adjust the adjusting nut: rotate clockwise to reduce the initial flow, and counterclockwise to increase the initial flow.