Brahma SM592N.2 36224431 gas controllers are designed for efficient operation with atmospheric gas burners and burners with a fan, having an independent (intermittent) mode of operation. All Brahma SM592N ionization control units.2 36224431 are equipped with a manual reset, which makes it possible to restart the installation by pressing the RESET button. The controllers have a CE certificate Reg. N° 51BT3691, conforming to Directives 90/396 and 93/68, as well as compliance with EN 298:2003, the European standard for gas burner control systems.

Technical information

Power Supply: Power Supply:110 V – 120 V – 50/60Hz

Operating temperature: -20 degrees to +60 degrees

Humidity: max. 95% at 40 degrees

Protection: IP 40

Time:

– Purge (TW): 1.5 sec

– Security (TS): 10 sec

– Pre-ventilation time (tv/tp): 1.5 sec

– Flame loss response: < 1 sec

Power consumption, at startup: 20 VA

Energy consumption during operation: 14 VA

Flame control:

– Min. Ionization current: 0.5 mA

– Recommended ionization current: 3-5 times more min. ionization current

– Max. cable length: 1 m.

Weight with the pad: 275g.

Dimensions: 8.5×6.8×6.5 cm

Installation Recommendations

• For technical and safety reasons, the system must be restarted every 24 hours (for systems with non-permanent gorenje).

• Connect and disconnect the controller only when the power supply is turned off.

• The controller is installed in any position.

• Avoid getting water droplets on the controller.

• Proper ventilation and operating temperature ensure a longer service life of the controller.

• Make sure that the type (code and time characteristics) of the controller are correct before installing or replacing.

Electrical connection

• The installation must comply with national requirements and European standards (e.g. EN 60335/1prEN 50165) for electrical safety.

• The phase and neutral must be connected correctly, an error can lead to dangerous situations. In case of non-compliance with the phase-neutral, the controller will operate in manual reset mode at the end of the start-up safety time.

• Before starting the system, carefully check the cable connections. An incorrect connection can damage the controller and compromise security.

• Check the grounding of the controller, the metal housing of the burner and the grounding of the main power supply.

• Ensure the distance between the ionization cable and the power cables/ignition cables.

• Use a well-insulated ionization electrode, protected from water and humidity.